51GB 01/2009 AWR MTD - AWR MTD/B
Low suction pressure
(less than 3.2 bars)*
Low utility water inlet temperature
Low outside water inlet temperature
Thermostatic expansion valve faulty or blocked
Blocked water filter
Blocked plate heat exchanger
Check
Low discharge pressure
(less than 12 bars)*
Low utility water inlet temperature
Check
Air in water circuit Vent
Insufficient refrigerant content Check
Moisture in the refrigerant circuit (flow indicator -
moisture yellow)
Empty and refill
Faulty operation of outside heat exchanger control
(pressure regulating valves)
Check
High suction pressure
(greater than 10 bars)*
High utility water inlet temperature
Thermostatic expansion valve faulty or excessively
open
Check
High discharge pressure
(greater than 23 bars)*
High outside water temperature
High utility water inlet temperature
Insufficient water flow-rate in outside heat exchanger
(cooling mode)
Insufficient water flow-rate in utility heat exchanger
(heating mode)
Check
Check pump operation
Faulty operation of outside heat exchanger control
(pressure regulating valves)
Check
Air in water circuit (heating mode) Vent
Excessive refrigerant content
Check
*Values indicative only
FAULT CAUSE SOLUTION
USEFUL INFORMATION
U I A
For information on technical assistance and obtaining spare parts, contact:
TECHNICAL SERVICE DEPARTMENT
CLIMAVENETA HOME SYSTEM S.R.L. ROOM AIR-CONDITIONING
via. L. Seitz, 47 - 31100 Treviso (ITALY)
www.climaveneta.it - [email protected]
Vue de la page 50
1 2 ... 46 47 48 49 50 51 52

Commentaires sur ces manuels

Pas de commentaire